This-fire-test-response standard covers the determination of the specific optical density of smoke generated by solid materials and assemblies mounted in the verticle position in thicknesses up to and including 1 inch. Measurement is made of the attenuation of a light beam by smoke accumulating within a closed chamber due to nonflamming pyrolytic dexomposition and flamming combustion. Results are expressed in terms of specific optical density which is derived from a geometrical factor and the measured optical density, a measurement characteristic of the concentration of the smoke.
Most specifications require the optical density of smoke to be 450 or less for acceptance.